Descriptions of
MTU Gas Generator Set:
1.Diesel engine configuration: alloy cast iron crankcase, replaceable cylinder
liner, high efficient plate cooler etc.
2. Adopt split-flow circulating cooling, three-wall water-cooled heat insulation
exhaust pipe, integrated attachment, and standard interface
3. State-of-the-art technology: lean burn, single-point injection, A/F ratio
closed-loop control
4. Small size, light weight, long life span
5. Can be fueled by natural gas, coal-mine gas, coal gas, methane etc.
6. 550KW and 1MW
gas generator set available from MTU brand
Applications of MTU Gas Generator Set:
This kind of CNG genset is widely used wherever gas can be gained at a
reasonable cost, such as oil fields and gas fields.
Gas Generator |
Genset |
||||
GAS GENERATOR |
8V165RQ |
16V165RQ |
GENSET MODEL |
CMQ550 |
CMQ1100 |
Power COP.(KW) |
630 |
1280 |
Rated power COP.(Kw) |
550 |
1100 |
Speed(r/min) |
150 |
Rated frequency(Hz) |
50 |
||
CRAMLOMG motor (kw/24VDC) |
9 |
15 |
Rated voltage(V) |
400/200 |
|
Oil consumpion of rated power(g/kw.h) |
<1.5 |
Rated current(A) |
992 |
1983 |
|
Cylinder |
8 |
16 |
Adjusting rate of voltage in stable state |
¡À5% |
|
Bore(mm) |
165 |
Fluctuating rate of voltage(%) |
1.5 |
||
Stock(mm) |
185 |
voltage regulation time(S) |
2 |
||
DISPLACEMENT(L) |
31.7 |
63.36 |
Adjusting rate of voltage in transient state (%) |
+25,-20 |
|
Compression rate |
11:1 |
Adjusting rate of frequency in stable state |
¡À8(%) |
||
Average effective pressure(Mpa) |
1.6 |
Adjusting rate of frequency in transient state(%) |
¡À18 |
||
Gas consumption rate(M3/h) |
175 |
350 |
Fluctuating rate of frequency |
2(%) |
|
|
|
|
Stable time of frequency |
15S |
|
|
|
|
Genset size(LxWxH) |
4856*1543*2100 |
|
|
|
|
Weight(kg) |
ca.4800 |
ca.11300 |